HV Cable Termination for Hazardous Areas
Based on the HVJB but suitable for 15kV, the ABJB can accept up to four phase connections in either a bottom entry or through box configuration.
The ABJB is manufactured from 316L (1.404) stainless steel. It is highly corrosion resistant and has been field-proven in some of the harshest industrial locations on the planet. Not only is the enclosure rated IP66 to EN 60529, it is also DTS-01 deluge tested.
As 11kV is the maximum allowable voltage under the IEC 60079-7 Increased Safety (Ex e) standard. The ABJB has been assessed in accordance with the Ex 's', special protection concept (IEC 60079-33) and carries dual ATEX and IECEx certification.
In line with the lower voltage HVJB, an ABJB-125 variant is available for the termination of multi-use cables. In this design, the power conductor compartment houses the HV cables. There is a separate control compartment for terminating fibre optic or control cables. The allows work to be carried out on optical fibres or control conductors without a need to isolate the HV supply.
-
IECEx approved using Ex s 'Special Protection'
-
Short time withstand 50kA for 1.0 second
-
Each compartment independently IP66
Standard Specification
Product Reference | Width (mm) | Height (mm) | Depth (mm) | Power Rating @ T4 (W) | Max Current (A) | Max No. of Ways | Weight (Kg) |
---|---|---|---|---|---|---|---|
EABJB-73(x-x) | 650 | 950 | 300 | 259 | 980 | 3 | 75 |
EABJB-83(x-x) | 800 | 1250 | 300 | 346 | 980 | 3 | 102 |
EABJB-84(x-x) | 800 | 1250 | 300 | 346 | 980 | 4 | 102 |
EABJB1253(x-x)LH | 1200 | 1250 | 300 | 346 | 980 | 3 | 120 |
EABJB1254(x-x)LH | 1200 | 1250 | 300 | 346 | 980 | 4 | 120 |
EABJB1253(x-x)RH | 1200 | 1250 | 300 | 346 | 980 | 3 | 120 |
EABJB1253(x-x)RH | 1200 | 1250 | 300 | 346 | 980 | 4 | 120 |