Compact Bulkhead & Exit Sign
The nD8611 is a compact LED bulkhead is designed for use in heavy industrial environments including process plants, refineries and bonded warehouses.
Compact and lightweight, this Zone 2 exit sign is ideal for building, walkway and stairwell escape route signage. The die-cast Aluminium bulkhead with integral battery backup provides instant 100% light output in emergency mode. It can run in maintained or non-maintained modes and features automatic battery monitoring and fault indication.
Available with self-adhesive running man decals, the nD8611 is compliant with ISO 7010 and ASR A1.3 (Viewing distance = 22m).
-
Compact and lighweight LED bulkhead with integral battery
-
Available with running man exit decal to ISO 7010
-
Also available for use with central battery systems
Luminaire Ratings
Product Reference | Integral Battery | Colour Temperature (K) | Lumen Output (lm) | Power (W) | Ambient Range | Weight (KG) |
---|---|---|---|---|---|---|
LX2ND8611201 | No | 6500 | 100 | 4W | -20°C to +40°C | 0.9 |
LX2ND86112013 | Yes | 6500 | 100 | 4W | -20°C to +40°C | 1.3 |
Note - Lumen output in Emergency mode is unchanged. Running man decal available to be ordered as an accessory.
Options
ZB | Preparation for use with a central battery system |
---|---|
RR | Looping facility (2 x M20 entries same side) |
ECG | 24V extra-low voltage |
60 | 60-minute emergency duration (100% output) |